• The FC2020.. (2-loop, expandable to 4) is a compact fire control panel with an integrated operating unit that can process signals from Sinteso devices of up to 252 addresses. The fire control panel can be used as a stand-alone version or networked.
• The control panel can be programmed with a user-friendly engineering tool (SintesoWorks) to create a system with great versatility. Up to 32 fire control panels and fire terminals can be connected in a single cluster (FCnet/SAFEDLINK network), or up to 16 panels when the cluster is connected to a danger management system. Using a fiber-optic backbone (FCnet/LAN) up to 14 of these clusters with up to 16 panels each can be networked. This topology enables the construction of an EN 54-compliant network with up to 64 fire control panels and fire terminals. Connection to Siemens Danger Management System. • All detector lines are monitored for ground faults. • Adaptation of the user text directly on the terminal or with the software engineering tool. Up to 2000 events can be stored according to various criteria. Automatic summer/winter time change. • Detection and automatic read-in (auto configuration) of all FDnet devices, providing immediate simple operation. Stored data can be uploaded via remote access (SintesoView). • The FC2020.. is ideally suited for smaller applications, e.g. in workshops, hotels, etc. or when networked as part of much larger applications. • The expansion and accessories must be ordered separately. Date Tehnice • Programmable input/output: 8 • Operating temperature: -8…+42°C • Storage temperature: -20…+60°C • Protection category: IP30 • Emergency power supply: up to 72 h (optional) • Detector compatibility: Sinteso • Relative humidity: ≤95% (no condensation) • Number of detector lines: 2 (4) loops or 4 (8) stub lines • Number of addresses: max. 252 • Plug-in position: 2 -> for serial interfaces RS232, RS485, 2 -> for network modules, 1 -> for loop extension (FDnet) • Color housing/cover: grey, ∼RAL 7035/white, ∼RAL 9010 |